[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-880014":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},880014,569,2,"多选题","某建筑的空调为一次泵水系统，夏季投入运行后发现，冷水泵的运行参数达到设计要求，且冷水机组并没有满负荷运行，但存在一些房间的实际温度高于设计值的现象。下列选项中，哪几项不是出现该现象的原因？",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","温度过高的房间的末端设备设计冷量不够",false,{"key":16,"text":17,"correct":18},"B","冷水机组的制冷安装容量不够",true,{"key":20,"text":21,"correct":14},"C","末端设备没有采取自动控制措施(或自控失灵)",{"key":23,"text":24,"correct":18},"D","冷水泵的总水流量不足","BD","",{"id":6,"name":28,"category":29,"favorite":30},"专业知识（暖通空调专业）","建筑工程",0]