[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-879983":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},879983,569,2,"多选题","下列关于热湿负荷的说法，哪几项是错误的?( )。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","某商业建筑的空调设计负荷可以小于实际运行中出现的最大负荷",false,{"key":16,"text":17,"correct":18},"B","某建筑冬季有分别需要供冷和供热的两个房间，应按两个房间净热抵消后的冷热量来选择冷热源",true,{"key":20,"text":21,"correct":18},"C","对于夏季需要湿度控制的工艺类空调，采用冷凝除湿后的空气与未处理前的空气进行热交换，可以显著减少再热量，但不会影响选择冷机的制冷量",{"key":23,"text":24,"correct":18},"D","对于室内仅有温度要求而无湿度要求的风机盘管加新风系统，空调系统的设计负荷可仅考虑显热负荷","BCD","选项A正确，有不保证小时数的概念；选项B条件不充分，错误，要看采用的空调系统形式才能确定能否冷热抵消后来选择冷热源；选项C错误，如果可以减少再热量，就会影响系统冷量；选项D不正确，在干燥地区是可以的。",{"id":6,"name":28,"category":29,"favorite":30},"专业知识（暖通空调专业）","建筑工程",0]