[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-879919":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},879919,569,2,"多选题","下列空调冷源设计中，不合理的是( )。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","空调冷负荷为500kW时，设置1台离心式冷水机组",true,{"key":16,"text":17,"correct":14},"B","要求机组制冷量从100%连续调节到10%的情况，选用2台离心式冷水机组",{"key":19,"text":20,"correct":21},"C","选择IPLV高的冷水机组",false,{"key":23,"text":24,"correct":14},"D","高档办公楼空调系统冷水机组设置3台，两用一备","ABD","两台螺杆机的调节性能、可靠性和部分负荷的性能通常比一台离心机好；离心机的调节范围较小；由于空调系统大多数时间工作在部分负荷状态下，因此应采用综合部分负荷性能系数(IPLV)来评价冷水机组的性能；舒适性空调的冷水机组不应考虑备份。",{"id":6,"name":28,"category":29,"favorite":30},"专业知识（暖通空调专业）","建筑工程",0]