[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-879880":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},879880,569,1,"单选题","热网的热水供热参数为95\u002F70℃，某建筑物热力入口处热网供水管的静压高度为60m，建筑物热力入口处的供回水压差大于室内采暖系统的压力损失，该建筑物顶层供水干管相对于热力人口热网供水管的高差为58m，下列哪一项连接方式是正确的？",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","直接连接",false,{"key":16,"text":17,"correct":14},"B","混水泵连接",{"key":19,"text":20,"correct":21},"C","采用板式换热器连接",true,{"key":23,"text":24,"correct":14},"D","采用减压阀连接","该建筑物顶层供水干管相对于热力入口热网供水管的高差为58m，所以静水压线应为58加3～5mH20，为61～63m，建筑物热力入口处热网供水管的静压高度为60m，静水压不满足要求，所以应采用板式换热器隔开两个系统。",{"id":6,"name":27,"category":28,"favorite":29},"专业知识（暖通空调专业）","建筑工程",0]