[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-879690":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},879690,568,2,"多选题","以下关于排水泵站设计的叙述中，哪些是正确的？( )",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","排水泵站宜分期建设，即泵房按近期规模设计，并按近期规模配置水泵机组",false,{"key":16,"text":17,"correct":18},"B","泵站室外地坪标高应按城市防洪标准确定",true,{"key":20,"text":21,"correct":18},"C","水泵宜选用同一型号，台数不应小于2台，不宜大于8台",{"key":23,"text":24,"correct":18},"D","当2台及2台以上水泵合用一根出水管时，每台泵的出水管上均应设置闸阀，并在闸阀和水泵之间设置止回阀","BCD","参见《室外排水设计规范》5.1.1条：排水泵站宜按远期规模设计，水泵机组可按近期规模配置。规范5.1.6条：泵站室外地坪标高应按城镇防洪标准确定，并符合规划部门要求。规范5.4.1条第1款：水泵宜选用同一型号，台数不应少于2台，不宜大于8台。当水量变化很大时，可配置不同规格的水泵，但不宜超过两种。规范5.5.1条：当2台或2台以上水泵合用一根出水管时，每台水泵的出水管上均应设置闸阀，并在闸阀和水泵之间设置止回阀。",{"id":6,"name":28,"category":29,"favorite":30},"专业知识（给排水）","建筑工程",0]