[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-879673":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},879673,568,2,"多选题","下述消火栓给水系统消防水泵房的设计要求中，哪几项不符合《建筑设计防火规范》的要求？( )",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","附设在民用建筑中的消防水泵房应采用防火墙与其他部位隔开",true,{"key":16,"text":17,"correct":14},"B","附设在民用建筑中的消防水泵房不应贴邻人员密集场所",{"key":19,"text":20,"correct":21},"C","消防水泵房内设置水泵的房间，应设排水设施",false,{"key":23,"text":24,"correct":14},"D","消防水泵房应采用乙级防火门","ABD","A项见《建筑设计防火规范》，表中防火墙的耐火等级为3h，而7.2.5条要求为2h；也就是说“耐火极限不低于2.00h的隔墙”与“防火墙”是两个概念；B项见第8.6.4条，消防水泵房设置在首层时，其疏散门宜直通室外；设置在地下层或楼层上时，其疏散门应靠近安全出口。安全出口属于人员密集场所。也就是说，本身并没有B项这样的说法；C项实际上是一般常识，消防泵房应设计排水、采暖、起重、通风、照明、通信等设拖；D项见第8.6.4条，消防水泵房的门应采用甲级防火门。",{"id":6,"name":28,"category":29,"favorite":30},"专业知识（给排水）","建筑工程",0]