[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-879670":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},879670,568,2,"多选题","某小区从城市给水环网东西两侧干管分别连接引入管，小区内室外给水干管与市政管网连接成环，引入管上水表前供水压力为0.25MPa(从地面算起)，若不计水表及小区内管网水头损失，则下述小区住宅供水方案中哪几项是正确合理的？( )",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","利用市政供水压力直接供至5层，6层及6层以上采用变频加压供水",false,{"key":16,"text":17,"correct":18},"B","利用市政供水压力直接供至4层，5层及5层以上采用变频加压供水",true,{"key":20,"text":21,"correct":14},"C","利用市政供水压力直接供至3层，4层及4层以上采用变频加压供水",{"key":23,"text":24,"correct":18},"D","利用市政供水压力直接供至4层，5层及5层以上采用水泵加高位水箱供水","BD","按照1层10m，2层12m，以后每隔一层次加4m的方法估算市政供水压力可供的楼层。《建筑给水排水设计规范》第3.2.5条：两路进水，且成环状时，应设倒流防止器，而倒流防止器的水损较大(见3.6.15条，03版规范是2.5～4m)，所以考虑此因素，只能满足4层的压力。",{"id":6,"name":28,"category":29,"favorite":30},"专业知识（给排水）","建筑工程",0]