[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-879668":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},879668,568,2,"多选题","某七氟丙烷管网灭火系统下列设计中，哪几项错误？( )",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","设置自动控制和手动控制两种启动方式",true,{"key":16,"text":17,"correct":14},"B","在防护区入口处设置手动与自动控制的转换开关",{"key":19,"text":20,"correct":14},"C","管道在进入各防护区处，设置选择阀",{"key":22,"text":23,"correct":24},"D","各喷头上标识有型号和规格",false,"ABC","依据《气体灭火系统设计规范》5.0.2条，管网灭火系统应设自动控制、手动控制和机械应急操作三种启动方式；预制灭火系统应设自动控制和手动控制两种启动方式。选项A中，还应设置机械应急操作，故错误。依据《气体灭火系统设计规范》5.0.5条，自动控制装置应在接到两个独立的火灾信号后才能启动；手动控制装置、手动与自动转换装置应设在防护区疏散出口的门外便于操作的地方，安装高度为中心点距地面1.5m；机械应急操作装置应设在储瓶间内或防护区疏散出口门外便于操作的地方。故B错误。依据《气体灭火系统设计规范》4.1.6条，组合分配系统中的每个防护区应设置控制灭火剂流向的选择阀，其公称直径应与该防护区灭火系统的主管道公称直径相等；选择阀的位置应靠近储存容器且便于操作。故C错误。",{"id":6,"name":28,"category":29,"favorite":30},"专业知识（给排水）","建筑工程",0]