[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-879662":3},{"question":4,"library":24},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":23},879662,568,2,"多选题","",[11,15,18,20],{"key":12,"text":13,"correct":14},"A","该给水系统设可调式减压阀分区不妥，应设比例式减压阀",false,{"key":16,"text":9,"correct":17},"B",true,{"key":19,"text":9,"correct":17},"C",{"key":21,"text":9,"correct":17},"D","BCD","A项在题中注明不考虑减压阀的安装方式的前提下，可调式与比例式的区别仅在于出口的压力是否允许波动，并且可调式能更好地达到效果；B项参见《技术措施》，2.5.11-4条，可调式减压阀的阀前与阀后的最大压差不应大于0.4MPa；要求环境安静的场所不应大于0.3MPa；阀前最低压力应大于阀后动压力0.2MPa；C项参见《建筑给水排水设计规范》第3.4.9-1条，可调式减压阀的阀前与阀后的最大压差不应大于0.4MPa；要求环境安静的场所不应大于0.3MPa，五星级酒店属于要求环境安静的场所；D项根据《建筑给水排水设计规范》第3.3.5.1条，各分区最低卫生器具配水点处的静水压不宜大于0.45MPA",{"id":6,"name":25,"category":26,"favorite":27},"专业知识（给排水）","建筑工程",0]