[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-879660":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},879660,568,2,"多选题","以下对于水喷雾系统的叙述，哪几项错误？( )",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","水喷雾与高压细水雾的灭火机理相同，喷头所需工作压力也基本相同",true,{"key":16,"text":17,"correct":18},"B","水喷雾灭火系统可用于扑救固定物质火灾外，还可适用于扑救丙类液体火灾、电气火灾等不宜用水灭火的场所",false,{"key":20,"text":21,"correct":14},"C","水喷雾系统属于闭式系统",{"key":23,"text":24,"correct":18},"D","水喷雾系统的供水控制阀，可采用雨淋报警阀、电动控制阀或气动控制阀等。但响应时间不大于120s的系统，应采用雨淋报警阀","AC","高压细水雾机理接近气体灭火，所需压力也更大，故A错误。依据《水喷雾灭火系统设计规范》1.0.3条，水喷雾灭火系统可用于扑救固体物质火灾、丙类液体火灾、饮料酒火灾和电气火灾，并可用于可燃气体和甲、乙、丙类液体的生产、储存装置或装卸设施的防护冷却。故B正确。水喷雾为开式系统，故C错误。依据《水喷雾灭火系统设计规范》4.0.4条，“当系统供水控制阀采用电动控制阀或气动控制阀时……”；依据《水喷雾灭火系统设计规范》4.0.3条，“按本规范的规定，响应时间不大于120s的系统，应设置雨淋报警阀组。”故D正确。",{"id":6,"name":28,"category":29,"favorite":30},"专业知识（给排水）","建筑工程",0]