[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-879648":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},879648,568,2,"多选题","下列关于气体灭火系统设计的叙述中，哪几项正确？( )",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","灭火系统的灭火剂储存量，应为最大防护区的灭火设计用量",false,{"key":16,"text":17,"correct":18},"B","设计管网上不应采用四通管件进行分流",true,{"key":20,"text":21,"correct":18},"C","灭火系统的设计温度，应采用20℃",{"key":23,"text":24,"correct":14},"D","扑灭气体类火灾的防护区，必须采用惰化设计浓度","BC","参见《气体灭火系统设计规范》3.1.6条可知A项错误；参见3.1.2条可知D项错误；参3.1.8条可知C项正确；参见3.1.11条可知B项正确。",{"id":6,"name":28,"category":29,"favorite":30},"专业知识（给排水）","建筑工程",0]