[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-879640":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},879640,568,2,"多选题","下列高层建筑室内临时高压消火栓给水系统的消防主泵房启、停控制方式中，哪几项是不正确的？( )",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","每个消火栓处应能直接启动消防主泵",false,{"key":16,"text":17,"correct":18},"B","消防控制中心应能手动启、停消防主泵",true,{"key":20,"text":21,"correct":14},"C","消防水泵房应能强制启、停消防主泵",{"key":23,"text":24,"correct":18},"D","消防水池最低水位应能自动停止消防水泵","BD","A项参见《高层建筑设计防火规范》第7.4.6.7条；B、C、D项参见《技术措施》P273，消防泵房应有强制启停泵按钮；消防控制中心应有手动启泵按钮；消防水池最低水位报警，但不得自动停泵；任何消防主泵不宜设置自动停泵的控制；B项为只能启动不能停泵，D项为不能自动停泵。",{"id":6,"name":28,"category":29,"favorite":30},"专业知识（给排水）","建筑工程",0]