[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-879625":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},879625,568,2,"多选题","以下哪几项不能作为计算居住小区给水设计用水量的依据？( )",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","居住小区给水设计最高日用水量应包括消防用水量",true,{"key":16,"text":17,"correct":18},"B","居住小区给水设计最高日用水量包括居住小区内的公共建筑用水量",false,{"key":20,"text":21,"correct":14},"C","居住小区给水的未预见水量按最高日用水量的10%～15%计",{"key":23,"text":24,"correct":14},"D","居住小区内重大公用设施的用水量应由某管理部门提出","ACD","此题为常识题。A项见《建筑给水排水设计规范》3.1.1条的注释；C项见《建筑给水排水设计规范》3.1.7条，是“漏损+未预见”两项取最高日用水量的10%～15%；D项见《技术措施》2.4.1-3条，或者是2003版《建筑给水排水设计规范》3.1.8条：“居住小区内的公用设施用水量，应由该设施的管理部门提供用水量，……”。注意：在2009规范中已经修改该条，加上了“计算参数”由管理部门提出。",{"id":6,"name":28,"category":29,"favorite":30},"专业知识（给排水）","建筑工程",0]