[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-879623":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},879623,568,2,"多选题","某宾馆(350床)高区生活给水系统拟采用如下供水方案：方案一：市政供水管→低位贮水池→变频增压设备→配水点。方案二：市政供水管→低位贮水池→增压水泵→高位水箱→配水点。下列关于上述方案一、方案二比较的叙述中，哪几项正确？( )",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","方案一、方案二的市政进水管设计流量可相同",true,{"key":16,"text":17,"correct":18},"B","方案一、方案二的增压供水设备设计流量可相同",false,{"key":20,"text":21,"correct":14},"C","方案一、方案二的低位贮水池设计有效容积可相同",{"key":23,"text":24,"correct":14},"D","方案一、方案二的生活给水系统配水管网设计流量可相同","ACD","依据《建筑给水排水设计规范》3.8.3条，建筑物内采用高位水箱调节的生活给水系统时，水泵的最大出水量不应小于最大小时用水量。依据规范3.8.4条，生活给水系统采用调速泵组供水时，应按系统最大设计流量选泵，调速泵在额定转速时的工作点，应位于水泵高效区的末端。可见，在有高位水箱时，规范没有规定水泵的最大出水量，但应小于系统最大设计流量，否则高位水箱的调节功能无效。故B错误。",{"id":6,"name":28,"category":29,"favorite":30},"专业知识（给排水）","建筑工程",0]