[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-879622":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},879622,568,2,"多选题","七氟丙烷及IG541混合气体灭火系统进行一次灭火的设计灭火剂储存量，应按下列哪几项之和进行确定？( )",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","防护区的灭火设计用量",true,{"key":16,"text":17,"correct":14},"B","储存容器内的灭火剂剩余量",{"key":19,"text":20,"correct":14},"C","管网内的灭火剂剩余量",{"key":22,"text":23,"correct":24},"D","按系统储存要求设置的备用量",false,"ABC","参见《气体灭火系统设计规范》第3.1.6条：“灭火系统的灭火剂储存量，应为防护区的灭火设计用量、储存容器内的灭火剂剩余量和管网内的灭火剂剩余量之和”。",{"id":6,"name":28,"category":29,"favorite":30},"专业知识（给排水）","建筑工程",0]