[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-879620":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},879620,568,2,"多选题","以下有关水加热设备选择的叙述中，哪几项是错误的？( )",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","容积式水加热设备被加热水侧的压力损失宜≤0.01MPa",false,{"key":16,"text":17,"correct":18},"B","医院热水供应系统设置2台不加热设备时，为确保手术室热水供水安全，一台检修时，另一台的供热能力不得小于设计小时耗热量",true,{"key":20,"text":21,"correct":18},"C","局部热水供应设备同时给多个卫生器具供热水时，因瞬时负荷不大，宜采用即热式加热设备",{"key":23,"text":24,"correct":14},"D","热水用水较均匀，热媒供应能力充足，可选用半容积式水加热器","BC","A项参见《建筑给水排水设计规范》第5.4.1.2条条文解释，建议水加热设备被加热水侧的阻力损失宜≤0.01MPa；B项参见《建筑给水排水设计规范》第5.4.3条条文解释，其余各台的总供应能力不得小于设计时耗热量的50%；C项参见《建筑给水排水设计规范》第5.4.4条，需同时供给多个卫生器具或设备热水时，宜选用带贮热容积的加热设备；D项参见《建筑给水排水设计规范》第5.4.2条条文说明第三款因素：用水较均匀，热媒供应能力充足，一般可选用贮热容积较小的半容积式水加热器，此项为正确项。",{"id":6,"name":28,"category":29,"favorite":30},"专业知识（给排水）","建筑工程",0]