[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-879613":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},879613,568,2,"多选题","关于建筑排水管道的布置与敷设，下面哪些项是正确的？( )",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","阳台地漏同时接纳雨水和洗衣机排水时应接至生活排水管道系统",true,{"key":16,"text":17,"correct":18},"B","医院无菌手术室的地面排水应采取间接排水方式",false,{"key":20,"text":21,"correct":14},"C","饮食业厨房及备餐的上方不得布置排水横管",{"key":23,"text":24,"correct":14},"D","集体宿舍盥洗室及淋浴间内应设置地漏","ACD","依据《建筑给水排水设计规范》4.8.8A条，住宅套内应按洗衣机位置设置洗衣机排水专用地漏或洗衣机排水存水弯，排水管道不得接入室内雨水管道。故A正确。洁净手术室内不应设置地漏，地漏应设置在刷手间及卫生器具旁且必须加密封盖，间接排水不行，故B错误。依据《建筑给水排水设计规范》4.3.6条，排水横管不得布置在食堂、饮食业厨房的主副食操作、烹调和备餐的上方；当受条件限制不能避免时，应采取防护措施。故C错误。依据《建筑给水排水设计规范》4.5.7条，厕所、盥洗室等需经常从地面排水的房间，应设置地漏。故D正确。",{"id":6,"name":28,"category":29,"favorite":30},"专业知识（给排水）","建筑工程",0]