[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-879606":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},879606,568,2,"多选题","",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","系统灭火剂设计用量按指挥中心设计用量确定",true,{"key":16,"text":17,"correct":14},"B","指挥中心的主机房、活动地板及吊顶内分别设一套管网",{"key":19,"text":20,"correct":21},"C","系统共设置5组启动钢瓶(其中，指挥中心设置3组启动钢瓶)",false,{"key":23,"text":24,"correct":14},"D","通向配电房、指挥中心、数据处理机房的主管道上分别设置选择阀、压力讯号器","ABD","根据《气体灭火系统设计规范》3.1.5条，可知A项正确；根据3.1.10条，可知B项正确，C项错误；根据4.1.5条及4.1.6条，可知D项正确。",{"id":6,"name":28,"category":29,"favorite":30},"专业知识（给排水）","建筑工程",0]