[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-879603":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},879603,568,2,"多选题","某电子计算机房分成三个防护区，采用七氟丙烷气体组合分配灭火系统，下列该系统灭火剂储存量的说明中，哪几项是正确的？( )",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","按三个防护区所需总储存量计算",false,{"key":16,"text":17,"correct":18},"B","按三个防护区中储存量最大的一个防护区所需储存量计算",true,{"key":20,"text":21,"correct":18},"C","灭火剂储存量应为最大防护区的灭火剂设计用量、储存容器及管网内灭火剂剩余量之和",{"key":23,"text":24,"correct":14},"D","灭火剂储存量均应按系统原储存量的100%设置备用量","BC","参见《气体灭火系统设计规范》3.1.5条，组合分配系统的灭火剂储存量，应按储存量最大的防护区确定；3.1.6条：灭火系统的灭火剂储存量，应为防护区的灭火设计用量与储存容器内的灭火剂剩余量和管网的灭火剂剩余量之和；3.1.7条：灭火系统的储存装置72小时内不能重新充装恢复工作的，应按系统原储存量的100%设置备用量。",{"id":6,"name":28,"category":29,"favorite":30},"专业知识（给排水）","建筑工程",0]