[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-879594":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},879594,568,2,"多选题","以下关于干式室内消火栓系统的叙述中，哪几项是正确的？( )",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","室内环境温度低于4℃时，为防止管内结冰，必须采用干式消火栓系统",false,{"key":16,"text":17,"correct":18},"B","由电动阀控制的干式消火栓灭火系统启动时，其开启时间不应超过30s",true,{"key":20,"text":21,"correct":18},"C","为使干式系统快速充水转换成湿式系统，在系统管道的最高处应设置快速排气阀",{"key":23,"text":24,"correct":18},"D","干式系统的管网充水时间不应大于5min","BCD","依据《消防给水及消火栓系统技术规范》7.1.3条，室内环境温度低于4℃或高于70℃的场所，宜采用干式消火栓系统。注意：是“宜”而不是“必须”，故A错误。依据《消防给水及消火栓系统技术规范》7.1.6条，干式消火栓系统的充水时间不应大于5min，并应符合下列规定：①在供水干管上宜设干式报警阀、雨淋阀或电磁阀、电动阀等快速启闭装置；当采用电动阀时开启时间不应超过30s；②当采用雨淋阀、电磁阀和电动阀时，在消火栓箱处应设置直接开启快速启闭装置的手动按钮；③在系统管道的最高处应设置快速排气阀。故B、C、D正确。",{"id":6,"name":28,"category":29,"favorite":30},"专业知识（给排水）","建筑工程",0]