[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-879584":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},879584,568,2,"多选题","某20层办公楼，层高3.0m，分高、中、低三层供水，低区为-2～4层，中区5～12层，高区13～20层，分区后各区最低层卫生器具配水点静水压力均小于350kPA以下叙述哪几项是正确的？( )",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","该楼各区最低层卫生器具配水点静水压力符合分区要求",true,{"key":16,"text":17,"correct":18},"B","该楼各区最低层卫生器具配水点静水压力不符合分区要求",false,{"key":20,"text":21,"correct":18},"C","分区后能满足各层卫生器具配水点最佳使用压力要求",{"key":23,"text":24,"correct":14},"D","分区后不能满足各层卫生器具配水点最佳使用压力要求","AD","参照《建筑给水排水设计规范》第3.3.5条，此建筑最底层卫生器具均不超过350kPa，分区最多层为8×3=24m，那么顶层压力为350-240=110kPa＞100kPA即A项明显正确。另外根据第3.3.5条条文说明，最佳使用水压为0.2～0.3MPa，因此不是所有层均可满足最佳水压要求。",{"id":6,"name":28,"category":29,"favorite":30},"专业知识（给排水）","建筑工程",0]