[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-879573":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},879573,568,2,"多选题","下列关于饮用净水的设计要求中，哪几项是正确的？( )",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","优先选用无高位水箱的供水系统",true,{"key":16,"text":17,"correct":18},"B","高层建筑饮用供水系统采用减压阀分区时，阀前应设置截污器",false,{"key":20,"text":21,"correct":18},"C","从配水立管接至配水龙头的管道长度不宜超过4m",{"key":23,"text":24,"correct":14},"D","管网最高处设置带有滤菌、防尘装置的排气阀","AD","A项参照《建筑给水排水设计规范》第5.7.3条条文说明；B项《建筑给水排水设计规范》第5.7.3条条文说明，因饮水水质好，减压阀前可不加截污器；C项《建筑给水排水设计规范》第5.7.3条条文说明，从立管接至配水龙头的支管管段长度应尽量短，一般不宜超过1m(09版规范为3m)；D项见《技术措施》3.3.10条：配水管网循环立管上端和下端应设阀门，供水管网应设检修阀门。在管网最低端应设排水阀，管道最高处应设排气阀。排气阀处应有滤菌、防尘装置。排水阀设置处不得有死水存留现象，排水口应有防污染措施。",{"id":6,"name":28,"category":29,"favorite":30},"专业知识（给排水）","建筑工程",0]