[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-879564":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},879564,568,2,"多选题","下列关于水泵接合器和室外消火栓设计的叙述中，哪几项错误？( )",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","墙壁消防水泵接合器距其墙面上的窗的净距为1.5m",true,{"key":16,"text":17,"correct":14},"B","十层住宅当设有室内消火栓时可不设室外消火栓",{"key":19,"text":20,"correct":14},"C","水泵接合器的数量应按室内外消防用水量之和计算确定",{"key":22,"text":23,"correct":24},"D","建筑室外消火栓的数量根据室外消火栓设计流量和保护半径计算确定",false,"ABC","依据《消防给水及消火栓系统技术规范》5.4.8条，墙壁消防水泵接合器的安装高度距地面宜为0.70m；与墙面上的门、窗、孔、洞的净距离不应小于2.0m，且不应安装在玻璃幕墙下方；地下消防水泵接合器的安装，应使进水口与井盖底面的距离不大于0.40m，且不应小于井盖的半径。故A错误。依据《消防给水及消火栓系统技术规范》5.4.3条，消防水泵接合器的给水流量宜按每个10～15L\u002Fs计算。每种水灭火系统的消防水泵接合器设置的数量应按系统设计流量经计算确定，但当计算数量超过3个时，可根据供水可靠性适当减少。即每个系统应分开计算，故C错误。依据《建筑设计防火规范》8.1.2条，城镇当居住区人数超过500人或者建筑层数超过两层的居住区，需设置消火栓。故B错误。",{"id":6,"name":28,"category":29,"favorite":30},"专业知识（给排水）","建筑工程",0]