[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-879520":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},879520,568,2,"多选题","下列有关自动喷水灭火系统设计的说法中，哪几项正确？( )",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","宾馆客房可采用边墙型喷头",true,{"key":16,"text":17,"correct":14},"B","预作用系统可替代干式系统",{"key":19,"text":20,"correct":14},"C","无报警阀组的局部应用系统，其配水管可直接与室内消火栓给水立管连接",{"key":22,"text":23,"correct":24},"D","当仓库顶板下及货架内均设有喷头时，系统设计流量按两者之间的最大值确定",false,"ABC","根据《自动喷水灭火系统设计规范》6.1.3.3条，宾馆客户属于中危1级，故A项正确；根据4.2.3条，可知B项正确；根据12.0.5条，可知C项正确；根据9.1.5条，设置货架内置喷头的仓库，顶板下喷头与货架内喷头应分别计算设计流量，并应按其设计流量之和确定系统的设计流量，可知D项错误。",{"id":6,"name":28,"category":29,"favorite":30},"专业知识（给排水）","建筑工程",0]