[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-879518":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},879518,568,2,"多选题","下列关于建筑灭火器设置要求的叙述中，哪几项正确？( )",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","一个计算单元内配置的灭火器数量不应少于2具",true,{"key":16,"text":17,"correct":18},"B","住宅建筑每层的公共部位应设置至少1具手提式灭火器",false,{"key":20,"text":21,"correct":14},"C","在A类火灾中危险级场所，单具Ms\u002F09型清水灭火器保护面积可达150㎡",{"key":23,"text":24,"correct":14},"D","E类火灾场所灭火器最低配置标准不应低于该场所内A类火灾的配置标准","ACD","参见《建筑灭火器配置设计规范》6.1.1条可知A项正确；参见6.1.3条可知小于100㎡可不设，故B项错误；参附录A可知Ms\u002F09的灭火级别为2A，参见6.2.1条可知中危级1A对应75㎡，故C项正确；参见6.2.4条可知D项正确。",{"id":6,"name":28,"category":29,"favorite":30},"专业知识（给排水）","建筑工程",0]