[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-879513":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},879513,568,2,"多选题","下列高层建筑消防给水系统竖向分区原则及水压的要求中，哪几项是正确的？( )",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","室内消火栓栓口的静水压力不应超过1.0MPa",true,{"key":16,"text":17,"correct":18},"B","室内消火栓栓口的进水压力不应超过0.5MPa",false,{"key":20,"text":21,"correct":14},"C","自动喷水灭火系统报警阀出口压力不应超过1.2MPa",{"key":23,"text":24,"correct":18},"D","自动喷水灭火系统轻、中危险级场所配水管道入口压力不应超过0.4MPa","AC","A、B项参见《高层建筑设计防火规范》第7.4.6.5条，消火栓栓口的静水压力不应大于1.00MPa；消火栓栓口的出水压力大于0.50MPa时；C项参见《自动喷水灭火系统设计规范》第8.0.1条，配水管道(参见术语中的2.1.16，配水管为配水干管、配水管、配水支管的总称)的工作压力不应大于1.20MPa；D项参照《自动喷水灭火系统设计规范》第8.0.5条，轻危险级、中危险级场所中各配水管入口的压力均不宜大于0.40MPa，此处为配水管而非配水管道。",{"id":6,"name":28,"category":29,"favorite":30},"专业知识（给排水）","建筑工程",0]