[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-879511":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},879511,568,2,"多选题","下列关于室内消防给水管道和消火栓布置的说法中，哪几项正确？( )",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","室内消防竖管直径不应小于DN100",false,{"key":16,"text":17,"correct":18},"B","消防电梯间前室内应设置消火栓",true,{"key":20,"text":21,"correct":14},"C","冷库内可不设置消火栓",{"key":23,"text":24,"correct":18},"D","","BD","参见《建筑设计防火规范》8.4.3条第2款可知B项正确；C项参见第4款“冷库内的消火栓应设置在常温穿堂或楼梯间内”，可知不是可不设置，而是设置的位置要做调整；参见规范8.4.3条第7款可知D项正确；选项A，参见规范8.3.1条第5款；“……当确有困难时，可只设置干式消防竖管……消防竖管的直径不应小于DN65”，参见规范8.4.2条第3款：“室内消防竖管直径不应小于DN100”。",{"id":6,"name":28,"category":29,"favorite":30},"专业知识（给排水）","建筑工程",0]