[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-879508":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},879508,568,2,"多选题","某医院的配电机房内采用预制式七氟丙烷气体灭火系统，在机房对角各设置一套预制式七氟丙烷气体灭火系统装置，以下关于该装置的设计，哪几项错误？( )",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","设自动控制和手动控制两种启动方式",false,{"key":16,"text":17,"correct":18},"B","每套装置上设置的气体喷头数量相同",true,{"key":20,"text":21,"correct":18},"C","每套装置的充压压力为4.2MPa",{"key":23,"text":24,"correct":14},"D","各装置能自行探测火灾并自动启动","BC","由《气体灭火系统设计规范》5.0.2条可知A项正确；参照国标图集，预制式七氟丙烷气体灭火系统无喷头，由柜子自带喷嘴喷放，所以B项错误；无管网系统钢瓶在防护区，因此压力不能太高，一般选2.5MPa，C项错误；参见《气体灭火系统设计规范》3.1.15条可知D项正确。本题有一定的实践性，对于没设计过类似工程确有困难。",{"id":6,"name":28,"category":29,"favorite":30},"专业知识（给排水）","建筑工程",0]