[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-879504":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},879504,568,2,"多选题","下列关于自动喷水灭火系统的叙述中，哪几项不正确？( )",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","雨淋报警阀不只限用于雨淋灭火系统",false,{"key":16,"text":17,"correct":14},"B","设有自动喷水灭火系统的房间，其吊顶内有时可不设喷头",{"key":19,"text":20,"correct":21},"C","预作用系统应在灭火喷头开启后立即自动向配水管道供水",true,{"key":23,"text":24,"correct":21},"D","配水管道的公称压力不应大于1.20MPa，并不应设置其他用水设施","CD","参见《自动喷水灭火系统设计规范》。A项，雨淋报警阀也用于预作用自动喷水灭火系统；B项，满足《自动喷水灭火系统设计规范》7.1.8条要设，也即不满足可不设；C项，见《自动喷水灭火系统设计规范》2.1.2.3条，对于预作用系统定又的理解；D项，见《自动喷水灭火系统设计规范》8.0.1条，“配水管道的工作压力不应大于1.20MPa，并不应设置其他用水设施”，而“公称压力”与“工作压力”不同。",{"id":6,"name":28,"category":29,"favorite":30},"专业知识（给排水）","建筑工程",0]