[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-879502":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},879502,568,2,"多选题","下列关于水喷雾灭火系统水雾喷头选型设计的叙述中，哪几项不正确？( )",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","扑救电气火灾应选用离心雾化型水雾喷头",false,{"key":16,"text":17,"correct":18},"B","用于扑救闪点高于60℃的液体火灾选用中速喷头",true,{"key":20,"text":21,"correct":18},"C","用于防护冷却容器的选用高速喷头",{"key":23,"text":24,"correct":14},"D","有粉尘场所设置的水雾喷头应设有防尘罩","BC","中速水雾喷头主要用于对需要保护的设备提供整体冷却保护，以及对火灾区附近的建、构筑物连续喷水进行冷却。高速水雾喷头具有雾化均匀、喷出速度高和贯穿力强的特点，主要用于扑救电气设备火灾和闪点在60℃以上的可燃液体火灾，也对可燃液体储罐进行冷却保护。《自动喷水灭火系统设计规范》提到：4.0.2水雾喷头的选型应符合下列要求；4.0.2.1扑救电气火灾应选用离心雾化型水雾喷头；4.0.2.2腐蚀性环境应选用防腐型水雾喷头；4.0.2.3粉尘场所设置的水雾喷头应有防尘罩。",{"id":6,"name":28,"category":29,"favorite":30},"专业知识（给排水）","建筑工程",0]