[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-879490":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},879490,568,2,"多选题","下列关于加(贮)热设备的布置，哪几项不正确？( )",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","空气源热泵机组的风机噪声大，应置于密闭的设有隔离材料的房间内",true,{"key":16,"text":17,"correct":14},"B","开式系统中冷水补给水箱最高设计水位应高于热水箱的最高设计水位",{"key":19,"text":20,"correct":21},"C","太阳能集热器的布置应保证每天4h的日照时间",false,{"key":23,"text":24,"correct":14},"D","热水机组一般露天布置，以使气流条件良好","ABD","空气源热泵机组需要良好的气流条件，因分机噪声大机组一般布置在屋顶或室外；机组不得布置在通风条件差、环境噪声控制严及人员密集的场所。故A错误。开式系统，冷水由冷水补给水箱经热水机组加热后先进入高位热水箱，因此冷水补给箱最低水位应高于高位热水箱最高水位。故B错误。热水机组不宜露天布置，宜与其他建筑物分离独立设置。故D错误。",{"id":6,"name":28,"category":29,"favorite":30},"专业知识（给排水）","建筑工程",0]