[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-879403":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},879403,568,2,"多选题","下列关于冷却塔热力计算的规定和表述中，正确的有哪几项？( )",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","冷却塔热力计算的设计任务就是冷却塔面积计算",false,{"key":16,"text":17,"correct":18},"B","冷却塔的热力计算宜采用焓差法或经验方法",true,{"key":20,"text":21,"correct":14},"C","计算冷却塔的最高冷却水温的气象资料，应采用近期连续不少于5年，每年最热时期3个月的月平均值。",{"key":23,"text":24,"correct":18},"D","计算冷却塔的各月的月平均冷却水温时，应采用近期连续不少于5年的相应各月的月平均气象条件","BD","A项，热力计算包括计算出水温度、求冷却塔面积或填料体积两大类。B项正确，冷却塔的热力计算方法可分为两类：一类是根据冷却塔内水和空气之间的热交换和物质交换过程，按蒸发冷却理论推导出来的理论公式计算法；另一类是按经验公式或图表的计算法。C项，含义是“日平均值”。D项正确，不少于5年的资料是必需的，另外资料要与要求计算的时间段统一起来。可参见《机械通风冷却塔工艺设计规范》相关内容。",{"id":6,"name":28,"category":29,"favorite":30},"专业知识（给排水）","建筑工程",0]