[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-879364":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},879364,568,2,"多选题","当水源取水泵房、净水设施及二级泵房能力有富余而清水池调节容量不足，水厂又无空地扩建清水池时，为满足用水需要可采用下列哪几项措施？( )",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","一级泵房水泵改为变频调速泵",false,{"key":16,"text":17,"correct":18},"B","在管网中增建调节构筑物",true,{"key":20,"text":21,"correct":14},"C","加大出厂配水管道能力",{"key":23,"text":24,"correct":18},"D","用水高峰时段增加取水泵房和净水设施流量","BD","因为取水泵房、净水设施、二级泵房能力富余，而且水池调节容量不足，就是说水源取水泵房和用户用水曲线之间(中间跳过了二级泵站供水曲线，从两头分析)的总体调节容积不足，故B项明显正确。另外，清水池调节有限，则在高峰用水时段增加进水量是明显有效的办法，所以D项也正确。A项不正确的原因是：采用变频调速泵，导致二级泵站供水曲线更趋向于用户曲线，意味着更偏离一级泵站的供水线，所以会更显得清水池调节容积不足。C项明显不正确，因为与清水池调节容积不足没有因果关系。",{"id":6,"name":28,"category":29,"favorite":30},"专业知识（给排水）","建筑工程",0]