[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-879280":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},879280,568,1,"单选题","下列关于雨水泵站的说法中，哪项不正确？( )",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","雨水泵站使用机会很少，可以在旱季检修，通常不设备用泵",false,{"key":16,"text":17,"correct":14},"B","雨水泵站通常流量大、扬程低，以使用轴流泵为主",{"key":19,"text":20,"correct":14},"C","集水池布置应尽量满足进水水流平顺和水泵吸水管安装条件",{"key":22,"text":23,"correct":24},"D","轴流泵的出水管上应安装闸阀，防止发生倒灌",true,"根据《室外排水设计规范》5.5.1条，雨水泵的出水管末端宜设防倒流装置，其上方宜考虑设置起吊设施。5.5.1条的条文解释：雨水泵出水管末端设置防倒流装置的目的是在水泵突然停运时，防止出水管的水流倒灌，或水泵发生故障时检修方便，我国目前使用的防倒流装置有拍门、堰门、柔性止回阀等。故D项错误。",{"id":6,"name":27,"category":28,"favorite":29},"专业知识（给排水）","建筑工程",0]