[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-879102":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},879102,568,1,"单选题","下述关于高层建筑生活给水系统的竖向分区要求中，哪项是错误的？( )",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","高层建筑生活给水系统竖向分区的配水管配水横管进口水压宜小于0.1MPa",true,{"key":16,"text":17,"correct":18},"B","生活给水系统竖向分区各区最低卫生器具配水点的静水压力，在特殊情况下不宜大于0.55MPa",false,{"key":20,"text":21,"correct":18},"C","生活给水系统不宜提倡以减压阀减压分区作为主要供水方式",{"key":23,"text":24,"correct":18},"D","竖向分区采取水泵直接串联供水方式，各级提升泵联锁，使用时先启动下一级泵，再启动上一级泵","A项是不宜小于0.1MPa，参见《建筑给水排水设计规范》3.3.5条说明。B项是规范原文。C、D项参见《全国民用建筑工程设计技术措施：给水排水》(2009年版)",{"id":6,"name":27,"category":28,"favorite":29},"专业知识（给排水）","建筑工程",0]