[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-879057":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},879057,568,1,"单选题","下列关于自动喷水灭火系统设计原则的叙述中，哪项错误？( )",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","雨淋系统中雨淋阀自动启动后，该阀所控制的喷头全部喷水",false,{"key":16,"text":17,"correct":14},"B","湿式系统中的喷头要能有效地探测初期火灾",{"key":19,"text":20,"correct":21},"C","预作用系统应在开放一只喷头后自动启动",true,{"key":23,"text":24,"correct":14},"D","在灭火进程中，作用面积内开放的喷头，应在规定的时间内按设计选定的喷水强度持续喷水","参见《自动喷水灭火系统设计规范》4.1.4条。自动喷水灭火系统的设计原则应符合下列规定：1.闭式喷头或启动系统的火灾探测器，应能有效探测初期火灾；2.湿式系统、干式系统应在开放一只喷头后自动启动，预作用系统、雨淋系统应在火灾自动报警系统报警后自动启动；3.作用面积内开放的喷头，应在规定时间内按设计选定的强度持续喷水。",{"id":6,"name":27,"category":28,"favorite":29},"专业知识（给排水）","建筑工程",0]