[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-879044":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},879044,568,1,"单选题","下列排水方式中，哪项错误？( )",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","某办公楼1～12层的卫生间设环形通气排水系统，首层卫生间排水接入排水立管",false,{"key":16,"text":17,"correct":18},"B","生活饮用水二次供水贮水池设于首层，水池溢流管(DN150)接入室外排水检查井，其管内底高于检查井设计水位300mm",true,{"key":20,"text":21,"correct":14},"C","住宅的厨房设置专用排水立管，各层厨房洗涤盆排水支管与排水立管相连接",{"key":23,"text":24,"correct":14},"D","办公楼职工餐厅厨房地面设排水明沟，洗碗机、洗肉池的排水排入该明沟","参见《建筑给水排水设计规范》4.3.12条，只要满足相应最小垂直距离要求并无不可，参见《建筑给水排水设计规范》4.6.5条条文解释中的图，就是首层接入排水立管，故A项正确；参见《建筑给水排水设计规范》4.3.13条，饮水池溢水管不得直接与污废水排水系统连接，排水检查井属于排水系统的一个组成部分，故B项错误；参见《建筑给水排水设计规范》4.3.6A条，住宅厨房设专用管并不不妥，故正C项正确；参见《建筑给水排水设计规范》4.3.16条，选项D并无不妥。",{"id":6,"name":27,"category":28,"favorite":29},"专业知识（给排水）","建筑工程",0]