[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-879040":3},{"question":4,"library":22},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":21},879040,568,1,"单选题","",[11,14,17,19],{"key":12,"text":9,"correct":13},"A",true,{"key":15,"text":9,"correct":16},"B",false,{"key":18,"text":9,"correct":16},"C",{"key":20,"text":9,"correct":16},"D","依据《消防给水及消火栓系统技术规范》8.2.3条，高压和临时高压消防给水系统的系统工作压力应根据系统在供水时，可能的最大运行压力确定，并应符合：采用高位消防水箱稳压的临时高压消防给水系统的系统工作压力，应为消防水泵零流量时的压力与水泵吸水口最大静水压力之和。参考《消防给水及消火栓系统技术规范》5.1.6条，消防水泵的选择和应用应符合：流量扬程性能曲线应为无驼峰、无拐点的光滑曲线，零流量时的压力不应大于设计工作压力的140%，且宜大于设计工作压力的120%。",{"id":6,"name":23,"category":24,"favorite":25},"专业知识（给排水）","建筑工程",0]