[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-878982":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},878982,568,1,"单选题","",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","1处",false,{"key":16,"text":17,"correct":14},"B","2处",{"key":19,"text":20,"correct":14},"C","3处",{"key":22,"text":23,"correct":24},"D","≥4处",true,"依据《建筑给水排水设计规范》3.4.10条，减压阀的设置应符合：①减压阀的公称直径宜与管道管径相一致。②减压阀前应设阀门和过滤器；需拆卸阀体才能检修的减压阀后，应设管道伸缩器；检修时阀后水会倒流时，阀后应设阀门。③减压阀节点处的前后应装设压力表。④比例式减压阀宜垂直安装，可调式减压阀宜水平安装。此外，依据《建筑给水排水设计规范》3.4.9条，给水管网的压力高于配水点允许的最高使用压力时，应设置减压阀，当在供水保证率要求高、停水会引起重大经济损失的给水管道上设置减压阀时，宜采用两个减压阀，并联设置，不得设置旁通管。故图中至少4处错误，选D",{"id":6,"name":27,"category":28,"favorite":29},"专业知识（给排水）","建筑工程",0]