[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-878978":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},878978,568,1,"单选题","下列关于高层建筑热水供应系统设计的叙述中，哪项错误？( )",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","热水供应系统分区应与冷水给水系统一致",false,{"key":16,"text":17,"correct":14},"B","热水供应系统采用的减压阀，其材质与冷水系统不同",{"key":19,"text":20,"correct":21},"C","采用减压阀分区的热水供应系统可共用第二循环泵",true,{"key":23,"text":24,"correct":14},"D","减压阀分区的热水供应系统不节能","参见《建筑给水排水设计规范》5.2.13条可知A项正确；参见该条第2款条文解释，可知密封部分材质不一样，故B正确；参见该条文解释，3个图，(a)不合理、(b)合理，不同区采用不同循环泵，(c)合理，但并未进行分区，其实所谓分区就是指“独立循环”，独立循环必须要有独立的循环泵，故C错误；减压阀人为按水压要求高处出水点压力要求提供压力，再把水压要求低处出水点水压入为降低，其就是能源浪费，故不节能。",{"id":6,"name":27,"category":28,"favorite":29},"专业知识（给排水）","建筑工程",0]