[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-878962":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},878962,568,1,"单选题","下列有关水喷雾灭火系统水雾喷头布置要求的叙述中，哪项错误？( )",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","当水喷雾保护输送机皮带时，喷头喷雾应完全包围输送机的机头、机尾和上、下行皮带",false,{"key":16,"text":17,"correct":14},"B","当水喷雾保护电缆时，喷头喷雾应完全包围电缆",{"key":19,"text":20,"correct":21},"C","当水喷雾保护液体储罐时，水雾喷头与保护液面之间的距离不应大于0.7m",true,{"key":23,"text":24,"correct":14},"D","当水喷雾保护油浸电力变压器时，水喷雾布置的垂直和水平间距应满足水雾锥相交的要求","A项见《水喷雾灭火系统设计规范》3.2.9条：当保护对象为输送机皮带时，喷雾应完全包围输送机的机头、机尾和上、下行皮带；B项见《水喷雾灭火系统设计规范》3.2.8条：当保护对象为电缆时，喷雾应完全包围电缆；C项见《水喷雾灭火系统设计规范》3.2.6条：当保护对象为可燃气体和甲、乙、丙类液体储罐时，水雾喷头与储罐外壁之间的距离不应大于0.7m。D项见3.2.5.3条：水雾喷头之间的水平距离与垂直距离应满足水雾锥相交的要求。",{"id":6,"name":27,"category":28,"favorite":29},"专业知识（给排水）","建筑工程",0]