[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-878945":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},878945,568,1,"单选题","下列关于建筑灭火器配置设计的叙述中，哪项不准确？( )",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","甲、乙类物品生产厂房灭火器应按严重危险配置",false,{"key":16,"text":17,"correct":14},"B","同一场所存在两种类型火灾，可配置同一类型通用型灭火器",{"key":19,"text":20,"correct":14},"C","灭火器箱可悬挂在墙壁或柱子上，但箱顶离地(楼)面的距离不应大于1.5m",{"key":22,"text":23,"correct":24},"D","对于危险等级相同的同一楼层或防火区分，可将其作为一个计算单元配置灭火器",true,"根据《建筑灭火器配置设计规范》7.2.1条，当一个楼层或一个水平防火分区内各场所的危险等级和火灾种类相同时，可将其作为一个计算单元。",{"id":6,"name":27,"category":28,"favorite":29},"专业知识（给排水）","建筑工程",0]