[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-878927":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},878927,568,1,"单选题","下列关于灭火器配置设计的叙述中，哪项不正确？( )",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","9层及以下的住宅建筑可不配置灭火器",false,{"key":16,"text":17,"correct":14},"B","选择灭火器时应考虑其使用人员的体能",{"key":19,"text":20,"correct":21},"C","同一防火分区内，灭火器的配置设计计算应相同",true,{"key":23,"text":24,"correct":14},"D","原木库房灭火器配置场所的危险等级不属于中危险级和严重危险级","参见《建筑灭火器配置设计规范》。A项参见该规范6.1.3条，公共部位面积不超过100㎡可不设，注意选项中的“可”字；B项参见该规范4.1.1.6条，“使用灭火器人员的体能”；C项参见该规范7.1.1条，“灭火器配置的设计与计算应按计算单元进行。”注意计算单位与防火分区的不同；D项参见附录C，原木库房、堆场灭火器配置场所的危险等级为轻危险级。",{"id":6,"name":27,"category":28,"favorite":29},"专业知识（给排水）","建筑工程",0]