[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-878900":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},878900,568,1,"单选题","下列关于高层建筑消火栓给水系统设计的叙述中，哪项不正确？( )",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","采用高压消防给水系统时，可不设高位消防水箱",false,{"key":16,"text":17,"correct":14},"B","建筑高度超过100m的民用建筑，室内消火栓系统应采用分区供水方式",{"key":19,"text":20,"correct":21},"C","高层建筑电梯间应设置室内消火栓",true,{"key":23,"text":24,"correct":14},"D","高层建筑室内外消火栓栓口处的水压不应小于0.10MPa","参见《高层民用建筑设计防火规范》7.4.7条可知A项正确；参见该规范7.4.6.5条可知B项正确(1.00MPa对应100m)；参见该规范7.4.6.8条，可知消防电梯间必设，其他电梯间不一定必设，故C错；参见该规范7.1.3条可知D项正确。",{"id":6,"name":27,"category":28,"favorite":29},"专业知识（给排水）","建筑工程",0]