[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-878885":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},878885,568,1,"单选题","某高层住宅室内消火栓给水系统采用临时高压系统，平时用高位水箱稳压，消防水泵设在地下室。该消火栓给水系统在下列哪项条件下应采用分区供水？( )",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","高位水箱的内底面与最低处消火栓栓口的高差为100m",true,{"key":16,"text":17,"correct":18},"B","高位水箱的最高水位与最低处消火栓栓口的高差为100m",false,{"key":20,"text":21,"correct":18},"C","消火栓给水泵的设计扬程为1.0MPa",{"key":23,"text":24,"correct":18},"D","消火栓给水泵出口的水压为1.0MPa","依据《消防给水及消火栓系统技术规范》6.2.1条，符合下列条件时，消防给水系统应分区供水：①系统工作压力大于2.40MPa；②消火栓栓口处静压大于1.0MPa；③自动水灭火系统报警阀处的工作压力大于1.60MPa或喷头处的工作压力大于1.20MPA。故A需分区。",{"id":6,"name":27,"category":28,"favorite":29},"专业知识（给排水）","建筑工程",0]