[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-878882":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},878882,568,1,"单选题","以下关于室内消火栓设置的叙述中，哪项不准确？( )",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","消防电梯前室应设消火栓",false,{"key":16,"text":17,"correct":14},"B","消火栓应设置在明显且易于操作的部位",{"key":19,"text":20,"correct":14},"C","消火栓栓口处的出水压力大于0.5MPa时，应设置减压设施",{"key":22,"text":23,"correct":24},"D","采用临时高压给水方式的室内每个消火栓处均应设置消防启动按钮",true,"D选项不满足《建筑设计防火规范》第8.4.3-8条：“高层厂房(仓库)和高位消防水箱静压不能满足最不利点消火栓水压要求的其他建筑，应在每个室内消火栓处设置直接启动消防水泵的按钮，并应有保护设施。”注意其中的含义，一是高层厂房(仓库)必然设置直接启动消防水泵的按钮，二是高位消防水箱静压不能满足最不利点消火栓水压要求的其他建筑才需要设置直接启动消防水泵的按钮。",{"id":6,"name":27,"category":28,"favorite":29},"专业知识（给排水）","建筑工程",0]