[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-878872":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},878872,568,1,"单选题","请判断油浸电力变压器设置水喷雾灭火系统时，下述各项设计技术要求中哪一项是错误的？( )",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","系统应采用撞击型水雾喷头，其工作压力应不小于0.35MPa",true,{"key":16,"text":17,"correct":18},"B","水雾喷头应布置在变压器的周围，不宜布置在变压器顶部",false,{"key":20,"text":21,"correct":18},"C","系统应设置自动控制、手动控制和应急操作三种控制方式",{"key":23,"text":24,"correct":18},"D","系统应采用雨淋阀，阀前管道应设置过滤器","A项见《水喷雾灭火系统设计规范》第4.0.2.1条及条文说明；应选用离心雾化喷头；B项3.2.5.1条；C项见6.0.1条；D项见第4.0.1条、第4.0.3.7条。",{"id":6,"name":27,"category":28,"favorite":29},"专业知识（给排水）","建筑工程",0]