[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-878868":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},878868,568,1,"单选题","下列关于建筑灭火器配置设计的叙述中，哪项错误？( )",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","灭火器可布置在楼梯间内",false,{"key":16,"text":17,"correct":14},"B","同一场所可配置两种以上类型灭火器，但其灭火剂应相容",{"key":19,"text":20,"correct":14},"C","灭火器的保护距离是指设置点到最不利点的直线行走距离",{"key":22,"text":23,"correct":24},"D","轻危险级场所应保证每个计算单元至少有一具灭火器保护",true,"参见《建筑灭火器配置设计规范》。A项参见5.1.1条条文说明，“沿着经常有人路过的建筑场所的通道、楼梯间、电梯间和出入口处设置灭火器，也是及时、就近取得灭火器的可靠保证之一”；B项参见4.1.3条，“在同一灭火器配置场所，当选用两种或两种以上类型灭火器时，应采用灭火剂相容的灭火器”；C项参见2.1.3条；D项参见6.1.1条，“一个计算单元内配置的灭火器数量不得少于2具”。",{"id":6,"name":27,"category":28,"favorite":29},"专业知识（给排水）","建筑工程",0]