[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-878862":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},878862,568,1,"单选题","下列有关自动喷水灭火系统操作与控制的叙述中，哪项错误？( )",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","雨淋阀采用充水传动管自动控制时，闭式喷头和雨淋阀之间的高差应限制",false,{"key":16,"text":17,"correct":14},"B","雨淋阀采用充气传动管自动控制时，闭式喷头和雨淋阀之间的高差不受限制",{"key":19,"text":20,"correct":21},"C","预作用系统自动控制是采用在消防控制室设手动远控方式",true,{"key":23,"text":24,"correct":14},"D","闭式系统在喷头动作后，应立即自动启动供水泵向配水管网供水","参见《自动喷水灭火系统设计规范》。C项错误，见4.1.4-2条：“湿式系统、干式系统应在开放一只喷头后自动启动，预作用系统、雨淋系统应在火灾自动报警系统报警后自动启动”。A、B项正确，见《自动喷水灭火系统设计规范》11.0.3条及条文说明。控制充液(水)传动管上闭式喷头与雨淋阀之间的高程差，是为了控制与雨淋阀连接的充液(水)传动管内的静压，保证传动管上闭式喷头动作后能可靠地开启雨淋阀。D项明显正确。",{"id":6,"name":27,"category":28,"favorite":29},"专业知识（给排水）","建筑工程",0]