[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-878805":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},878805,568,1,"单选题","某厂(在非多风地区)选用多个同规格的双侧进风逆流式机械通风冷却塔，其每格进风口高1.5m，由于地形限制，采用长轴不在同一直线的三排平面布置。下列表述错误的是哪项？( )",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","塔的进风面宜平行于夏季主导风向",false,{"key":16,"text":17,"correct":14},"B","不同排冷却塔进风口之间的距离不小于6m",{"key":19,"text":20,"correct":21},"C","进风口宜设百叶窗式导风装置",true,{"key":23,"text":24,"correct":14},"D","冷却塔填料底部至集水池之间宜设挡风隔板","根据《工业循环水冷却设计规范》2.2.6条，可知A项正确；根据2.2.8条，B项正确。根据2.2.18条，C项错误；根据2.2.17条，D项正确。",{"id":6,"name":27,"category":28,"favorite":29},"专业知识（给排水）","建筑工程",0]